Central Site Remote Access Switch 45
H
ARDWARE
O
VERVIEW
System Platforms
CAUTION FOR DC-POWERED CSX5500S
Connect to a reliably-grounded SELV source.
Use branch circuit overcurrent protection rated at 15A only.
Use 12 or 14 AWG conductors only.
Incorporate a readily-accessible disconnect device in the field wiring that is suitably ap-
proved and rated.
Install in a restricted access area in accordance with the NEC or the authority having juris-
diction.
To reduce the risk of electrical shock or energy hazards:
!